Effective virus air purification: Model variants and special solutions
TAC high-performance air purifiers – professional Trotec solutions for virus filtration and air pollution control
No other method than the HEPA high-performance filter technology provides "as much clean air for quickly diluting the aerosol clouds" with increased safety for the optimum price/clean air ratio!
To ensure that you're always provided with the precisely-tailored Trotec solution for effective virus filtration of the room air, exactly adapted to your individual safety requirement, in addition to the high-performance air purifier TAC V+ our range of products contains further model variants and special solutions.
To help you integrate the TAC V+ into the respective application environment, in addition to the standard colour yellow, this device is also available painted in the colours basalt grey, white or bronze.
Moreover, a stainless steel version is available for the use in hygiene-sensitive areas – and for virus air filtration in large halls we can offer you the special model TAC V+ Dual for wall or ceiling mounting, which blows out clean air to both sides.
Mobile or stationary: HEPA-filtered clean air wherever it is needed
TAC high-performance air purifiers are all guarantors for clean, filtered and pure air. And the configuration options of this air cleaner series are just as variable as the individual requirement situation on site. In addition to the mobile version, all TAC high-performance air purifiers can also be supplied as stationary tower versions. While the mobile version offers you maximum flexibility for situational room and location changes, the stationary tower version convinces with HEPA-filtered clean air at a fixed installation site. All versions have an optimised housing design in common, which fits stylishly and discreetly into any living environment.
Stylish design – unrivalled quietness
Whether it's the stylish design housing of the tower version or the conveniently transportable mobile variant, both versions use the same air purification technology. Whichever exterior you prefer, the interior is always 100 % the TAC high-performance air purifier of your choice.
While the mobile versions TAC V + and TAC M are delivered with an installed blow-out tower as standard, the mobile version of the TAC ECO and the stationary tower versions are with a ceiling-facing exhaust hood. Only the TAC V+ is supplied with a blowing-out tower instead of a discharge hood as standard. This also applies to the tower version due to the thermal decontamination function of the device.
All models – whether mobile or stationary – have been subjected to an elaborate sound insulation concept and are now equipped with an integral silencer on the suction side as standard equipment. All in all, this makes the new TAC generation hardly noticeable in everyday use.
Compared to competitive stationary models, the tower version of the TAC is 50 % smaller and 50 % lighter, yet more robust – and 100 % more stylish. Due to the integrated furniture castors, the stationary tower version of the TAC is far easier to move than other stationary air cleaners.
Variable configuration options – custom-fit application possibilities
All TAC high-performance air purifiers can be adapted to suit your individual on-site room situation. For high ceilings, the discharge level can be increased variably by installing one or two optional FlowExtender Silence+. Increased discharge level, reduced noise level: Each of these accessory spacers increases the height of the room air cleaner by 50 cm and additionally enables sound insulation of the discharge air flow by approx. 2 to 3 dB.
100 % TAC V+ on the outside, modified to meet your requirements on the inside: Model variants TAC M, TAC ECO and TAC BASIC
The model variants TAC M, TAC ECO and TAC BASIC are the perfect combination of the scientifically confirmed effective H14 HEPA virus filtration of the TAC V+ and your individual economic requirements, without having to forego any basic equipment features of the high-performance air purifier TAC V+.
The criteria for an effective virus air cleaner required by science are:
- The device must have a sufficiently large volumetric flow. at least six times the room volume per hour
- The device must be technically capable of removing 99.995 % of the viruses in the course of one air cycle, as can be ensured by an H14 HEPA filter complying with EN 1822
- The device must be quiet so that it does not disturb people inside the room, otherwise there is a risk of the device being switched off by the user
All these criteria are fully met not only by the TAC V+, but also by the TAC M, TAC ECO and TAC BASIC. This is why the air cleaners TAC M, TAC ECO and TAC BASIC are our best recommendation if you want to do without the full equipment of the TAC V+, but not without effective H14 HEPA virus filtration from Trotec "made in Germany".
Since the high-performance air purifiers TAC M and TAC ECO do not have a function for thermal decontamination and filter regeneration, they can also be used in areas which, due to electrical protection, only permit automated thermal decontamination to a limited extent. Consequently, the devices come without the added value of thermal room decontamination – maximum hygiene and safety –, which is offered by the TAC V+ through cyclic heat inactivation and thermal filter self-cleaning for longer filter lifetimes.
TAC M – TAC V+-like virus-filtered clean air
Being equipped with a programmable touch display incl. USB update function just like the TAC V+, the TAC M offers you convenient configuration options. Furthermore, you also benefit from the integrated FlowMatic control for a constant air volume flow at any power level with the TAC M. On request, the TAC M can be ordered in all colours available for the TAC V+.
TAC ECO – virus-filtered clean air, manually adjusted
The TAC ECO is the perfect reduction of the TAC V+ to its essential virus filter qualities with an H14 HEPA filter standard according to EN 1822. Once manually configured, you also benefit automatically from virus-filtered clean air in your rooms with the TAC ECO – thanks to the silent function of the TAC V+ and TAC M which can also be switched on and off with a flip switch. The TAC ECO is only available in light grey.
TAC BASIC – the best basis for virus-filtered clean air
With the exception of the filter change indicator, the TAC BASIC comes with all the basic functions of the TAC ECO, but is only available as a stationary tower version which can also be used as a mobile device thanks to the installed furniture castors.
Multi air handler TAC XT
For expanded fields of application of the TAC V+ beyond air pollution control, the multi air handler TAC XT was developed.
The multi air handler TAC XT is based on the same assembly as the TAC V+, which is why it is provided with an identical HEPA air purification function with filter class H14 and a filter efficiency of 99.995 %.
In addition, the multi air handler TAC XT can also be used for combined room heating as well as thermal pest control and thermal decontamination of viruses, for example for decontamination of sanitary facilities, dressing rooms, etc. during the night, or for the flexible, reliable decontamination of respiratory masks and disposable PSA equipment for multiple use.
Possible applications and equipment differences of TAC high-performance air purifiers at a glance
Trotec high-performance air purifiers with HEPA H14 suitability in compliance with EN 1822 (corresponds to ISO 45 H according to ISO 29463) | |||||
---|---|---|---|---|---|
TAC XT | TAC V+ | TAC M | TAC ECO | TAC BASIC | |
Use for high-performance H14 HEPA air purification as per EN 1822 | ✓ | ✓ | ✓ | ✓ | ✓ |
Integral silencer | ✓ | ✓ | ✓ | ✓ | ✓ |
Stationary stand version | – | ✓ | ✓ | ✓ | ✓ |
Mobile carriage design | ✓ | ✓ | ✓ | ✓ | – |
Usage-related filter change indicator for prefilter and HEPA filter | ✓ | ✓ | ✓ | ✓ | – |
FlowMatic volumetric flow control | ✓ | ✓ | ✓ | – | – |
Programmable touch display updateable via USB | ✓ | ✓ | ✓ | – | – |
Thermal filter decontamination and filter regeneration | ✓ | ✓ | – | – | – |
Use for room heating, tent heating (heating capacity 18/27 kW) | ✓ | – | – | – | – |
Use for thermal decontamination of rooms and objects | ✓ | – | – | – | – |
Use for thermal disinfestation | ✓ | – | – | – | – |
Trotec high-performance air purifiers with HEPA H14 suitability in compliance with EN 1822 (corresponds to ISO 45 H according to ISO 29463) | TAC XT | TAC V+ | TAC M | TAC ECO | TAC BASIC |
---|---|---|---|---|---|
Use for high-performance H14 HEPA air purification as per EN 1822 | ✓ | ✓ | ✓ | ✓ | ✓ |
Integral silencer | ✓ | ✓ | ✓ | ✓ | ✓ |
Stationary stand version | – | ✓ | ✓ | ✓ | ✓ |
Mobile carriage design | ✓ | ✓ | ✓ | ✓ | – |
Usage-related filter change indicator for prefilter and HEPA filter | ✓ | ✓ | ✓ | ✓ | – |
FlowMatic volumetric flow control | ✓ | ✓ | ✓ | – | – |
Programmable touch display updateable via USB | ✓ | ✓ | ✓ | – | – |
Thermal filter decontamination and filter regeneration | ✓ | ✓ | – | – | – |
Use for room heating, tent heating (heating capacity 18/27 kW) | ✓ | – | – | – | – |
Use for thermal decontamination of rooms and objects | ✓ | – | – | – | – |
Use for thermal disinfestation | ✓ | – | – | – | – |
TAC high-performance air purifiers – more technical data at a glance | |||||
---|---|---|---|---|---|
TAC XT | TAC V+ | TAC M | TAC ECO | TAC BASIC | |
Max. air flow rate heating (without HEPA filter) | 2,500 m³/h | - | - | - | - |
Max. air volume flow for the respective filter class |
with HighFlow H14 HEPA Heat Resistant filter: H14 ≤ 1,200 m³/h, H13 ≤ 2,100 m³/h |
H14 ≤ 1,000 m³/h H13 ≤ 1,600 m³/h |
|||
Prefilter | G4 Z-line (EN 779:2002) |
F7 (EN 779:2002), ePM10 85 % (ISO 16890) | G4 Z-line (EN 779:2002) |
||
High-temperature particulate air filter |
TROTEC HEPA H14 HighFlow Heat Resistant filter, EN 1822 Fully encapsulated H14 HighFlow metal lamellae high-temperature filter “made in Germany” Each filter is tested and certified individually. |
TROTEC HEPA H14, EN 1822 (standard minipleat) Each filter is tested and certified individually. |
|||
Filter change interval |
approx. 2 to 4 years (depending on the application and with regular thermal decontamination) |
approx. 1 to 3 years (depending on the application) |
approx. 1 to 2 years (depending on the application) |
max. 1 to 2 years | |
Filter change indication | Usage-related, sensor-controlled filter change indicator for prefilter and HEPA filter | - | |||
FlowMatic control |
Constant clean air volume flow, constant circulation rates in each power level also with increasing filter contamination. Air volume freely adjustable in m³. |
– | |||
Safety and filter hygiene: Thermal decontamination and filter regeneration at approx. 100 °C. 15 min. heating-up phase / 15 min. decon phase (altogether 30 min.) |
Time freely programmable, the thermal decontamination and filter regeneration process takes place fully automatically, usually once a week at night or outside business or teaching hours. Thermal decontamination and filter regeneration can be switched off temporarily or even constantly as required. Due to the short treatment duration (15 min.) and the low energy input (altogether approx. 1.0 kWh per cycle), the room temperature does not increase by thermal decontamination. |
No thermal decontamination and reconditioning of the filter |
|||
Mains connection (connector plug) | 380–480 V 50 / 60 Hz (CEE 32 A) | 220–240 V 50 / 60 Hz (CEE 7/7, H07RN-F) | |||
ø power consumption |
Air purification: 0.15 kW*, 1.25 kW (short-term peak load, e.g. once a week during thermal decontamination)
heating: max. 27 kW |
0.15 kW*, 1.25 kW (short-term peak load, e.g. once a week during thermal decontamination) |
0.15 kW* | ||
Exemplary total energy consumption (with 900 m³/h air volume) |
Without thermal decontamination approx. 1.2 kWh per day / approx. 24 kWh per month* With thermal decontamination approx. 1.4 kWh per day / approx. 28 kWh per month* and thermal decontamination once a week |
approx. 1.2 kWh per day / approx. 24 kWh per month* |
|||
Control panel | Programmable, USB updateable touch display with PIN-protected lock function | Manual control panel (6-step switch) | |||
Dimensions L x W x H With wheels and handle (mobile housing) |
690 mm x 630 mm x 1,300 mm to 2,300 mm ** Width with optional sound protection caps: 770 mm |
690 mm x 630 mm x 1,130 mm to 2,300 mm ** Width with optional sound protection caps: 770 mm |
– | ||
Dimensions L x W x H (stationary housing) |
– |
506 x 523 x 1,100 mm to 2,300 mm ** |
|||
Width with optional sound protection caps: 770 mm | |||||
Weight (mobile housing) |
TAC XT 18: |
89 kg (incl. filter) | 86 kg (incl. filter) | 83 kg (incl. filter) | – |
Weight (stationary housing) |
– | 85 kg (incl. filter) | 81 kg (incl. filter) | 78 kg (incl. filter) | 73 kg (incl. filter) |
* for a 5-day week with 8 h operating time per day and 900 m³ air volume ** depending on the FlowExtender Silence+ attachment |
TAC XT |
Max. air flow rate heating (without HEPA filter) |
2,500 m³/h |
Max. air volume flow for the respective filter class |
with HighFlow H14 HEPA Heat Resistant filter: H14 ≤ 1,200 m³/h, H13 ≤ 2,100 m³/h |
Prefilter |
G4 Z-Line (EN 779:2002) |
High-temperature particulate air filter |
TROTEC HEPA H14 HighFlow Heat Resistant filter, EN 1822 Fully encapsulated H14 HighFlow metal lamellae high-temperature filter “made in Germany” (optional also as Ultra-HighFlow filter). Each filter is tested and certified individually. |
Filter change interval |
Approx. 2 to 4 years (depending on the application and with regular thermal decontamination) |
Filter change indication |
Usage-related, sensor-controlled filter change indicator for prefilter and HEPA filter |
FlowMatic control |
Constant clean air volume flow, constant circulation rates in each power level also with increasing filter contamination. Air volume freely adjustable in m³. |
Safety and filter hygiene: Thermal decontamination and filter regeneration at approx. 100 °C. 15 min. heating-up phase / 15 min. decon phase (altogether 30 min.) |
Time freely programmable, the thermal decontamination and filter regeneration process takes place fully automatically, usually once a week at night or outside business or teaching hours. Thermal decontamination and filter regeneration can be switched off temporarily or even constantly as required. Due to the short treatment duration (15 min.) and the low energy input (altogether approx. 1.0 kWh per cycle), the room temperature does not increase by thermal decontamination. |
Mains connection (connector plug) |
380–480 V 50 / 60 Hz (CEE 32 A) |
ø power consumption |
Air purification: 0.15 kW*, 1.25 kW (short-term peak load, e.g. once a week during thermal decontamination)
heating: max. 27 kW |
Exemplary total energy consumption (with 900 m³/h air volume) |
Without thermal decontamination approx. 1.2 kWh per day / approx. 24 kWh per month* With thermal decontamination approx. 1.4 kWh per day / approx. 28 kWh per month* and thermal decontamination once a week |
Control panel |
Programmable, USB updateable touch display with PIN-protected lock function |
Dimensions L x W x H (mobile housing) |
With wheels and handle: 690 mm x 630 mm x 1,300 mm to 2,300 mm ** Width with optional sound protection caps: 770 mm |
Dimensions L x W x H (stationary housing) |
– |
Weight (mobile housing) |
TAC XT 18: 104 kg (incl. Filter) TAC XT 27: 109 kg (incl. Filter) |
Weight (stationary housing) |
– |
* for a 5-day week with 8 h operating time per day and 900 m³ air volume ** depending on the FlowExtender Silence+ attachment |
TAC V+ |
Max. air flow rate heating (without HEPA filter) |
- |
Max. air volume flow for the respective filter class |
with HighFlow H14 HEPA Heat Resistant filter: H14 ≤ 1,200 m³/h, H13 ≤ 2,100 m³/h |
Prefilter |
F7 (EN 779:2002), ePM10 85 % (ISO 16890) |
High-temperature particulate air filter |
TROTEC HEPA H14 HighFlow Heat Resistant filter, EN 1822 Fully encapsulated H14 HighFlow metal lamellae high-temperature filter “made in Germany” (optional also as Ultra-HighFlow filter). Each filter is tested and certified individually. |
Filter change interval |
Approx. 2 to 4 years (depending on the application and with regular thermal decontamination) |
Filter change indication |
Usage-related, sensor-controlled filter change indicator for prefilter and HEPA filter |
FlowMatic control |
Constant clean air volume flow, constant circulation rates in each power level also with increasing filter contamination. Air volume freely adjustable in m³. |
Safety and filter hygiene: Thermal decontamination and filter regeneration at approx. 100 °C. 15 min. heating-up phase / 15 min. decon phase (altogether 30 min.) |
Time freely programmable, the thermal decontamination and filter regeneration process takes place fully automatically, usually once a week at night or outside business or teaching hours. Thermal decontamination and filter regeneration can be switched off temporarily or even constantly as required. Due to the short treatment duration (15 min.) and the low energy input (altogether approx. 1.0 kWh per cycle), the room temperature does not increase by thermal decontamination. |
Mains connection (connector plug) |
220–240 V 50 / 60 Hz (CEE 7/7, H07RN-F) |
ø power consumption |
0.15 kW*, 1.25 kW (short-term peak load, e.g. once a week during thermal decontamination) |
Exemplary total energy consumption (with 900 m³/h air volume) |
Without thermal decontamination approx. 1.2 kWh per day / approx. 24 kWh per month* With thermal decontamination approx. 1.4 kWh per day / approx. 28 kWh per month* and thermal decontamination once a week |
Control panel |
Programmable, USB updateable touch display with PIN-protected lock function |
Dimensions L x W x H (mobile housing) |
With wheels and handle: 690 x 630 x 1,300 mm to 2,300 mm ** Width with optional sound protection caps: 770 mm |
Dimensions L x W x H (stationary housing) |
506 x 523 x 1,100 mm to 2,300 mm ** Width with optional sound protection caps: 770 mm |
Weight (mobile housing) |
89 kg (incl. Filter) |
Weight (stationary housing) |
85 kg (incl. Filter) |
* for a 5-day week with 8 h operating time per day and 900 m³ air volume ** depending on the FlowExtender Silence+ attachment |
TAC M |
Max. air flow rate heating (without HEPA filter) |
- |
Max. air volume flow for the respective filter class |
with HighFlow H14 HEPA Heat Resistant filter: H14 ≤ 1,200 m³/h, H13 ≤ 2,100 m³/h |
Prefilter |
F7 (EN 779:2002), ePM10 85 % (ISO 16890) |
High-temperature particulate air filter |
TROTEC HEPA H14 HighFlow Heat Resistant filter, EN 1822 Fully encapsulated H14 HighFlow metal lamellae high-temperature filter “made in Germany” (optional also as Ultra-HighFlow filter). Each filter is tested and certified individually. |
Filter change interval |
Approx. 1 to 3 years (depending on the application) |
Filter change indication |
Usage-related, sensor-controlled filter change indicator for prefilter and HEPA filter |
FlowMatic control |
Constant clean air volume flow, constant circulation rates in each power level also with increasing filter contamination. Air volume freely adjustable in m³. |
Safety and filter hygiene: Thermal decontamination and filter regeneration at approx. 100 °C. 15 min. heating-up phase / 15 min. decon phase (altogether 30 min.) |
No thermal decontamination and reconditioning of the filter |
Mains connection (connector plug) |
220–240 V 50 / 60 Hz (CEE 7/7, H07RN-F) |
ø power consumption |
0.15 kW* |
Exemplary total energy consumption (with 900 m³/h air volume) |
approx. 1.2 kWh per day / approx. 24 kWh per month* |
Control panel |
Programmable, USB updateable touch display with PIN-protected lock function |
Dimensions L x W x H (mobile housing) |
With wheels and handle: 690 x 630 x 1,300 mm to 2,300 mm ** Width with optional sound protection caps: 770 mm |
Dimensions L x W x H (stationary housing) |
506 x 523 x 1,100 mm to 2,100 mm ** Width with optional sound protection caps: 770 mm |
Weight (mobile housing) |
86 kg (incl. Filter) |
Weight (stationary housing) |
81 kg (incl. Filter) |
* for a 5-day week with 8 h operating time per day and 900 m³ air volume ** depending on the FlowExtender Silence+ attachment |
TAC ECO |
Max. air flow rate heating (without HEPA filter) |
- |
Max. air volume flow for the respective filter class |
H14 ≤ 1,000 m³/h H13 ≤ 1,600 m³/h |
Prefilter |
G4 Z-line (EN 779:2002) |
High-temperature particulate air filter |
TROTEC HEPA H14, EN 1822 (standard minipleat) Each filter is tested and certified individually. |
Filter change interval |
Approx. 1 to 2 years(depending on the application) |
Filter change indication |
Usage-related, sensor-controlled filter change indicator for prefilter and HEPA filter |
FlowMatic control |
– |
Safety and filter hygiene: Thermal decontamination and filter regeneration at approx. 100 °C. 15 min. heating-up phase / 15 min. decon phase (altogether 30 min.) |
No thermal decontamination and reconditioning of the filter |
Mains connection (connector plug) |
220–240 V 50 / 60 Hz (CEE 7/7, H07RN-F) |
ø power consumption |
0.15 kW* |
Exemplary total energy consumption (with 900 m³/h air volume) |
approx. 1.2 kWh per day / approx. 24 kWh per month* |
Control panel |
Manual control panel (6-step switch) |
Dimensions L x W x H (mobile housing) |
With wheels and handle: 690 x 630 x 1,130 mm to 2,300 mm ** Width with optional sound protection caps: 770 mm |
Dimensions L x W x H (stationary housing) |
506 x 523 x 1,100 mm to 2,100 mm ** Width with optional sound protection caps: 770 mm |
Weight (mobile housing) |
83 kg (incl. Filter) |
Weight (stationary housing) |
78 kg (incl. Filter) |
* for a 5-day week with 8 h operating time per day and 900 m³ air volume ** depending on the FlowExtender Silence+ attachment |
TAC BASIC |
Max. air flow rate heating (without HEPA filter) |
- |
Max. air volume flow for the respective filter class |
H14 ≤ 1,000 m³/h H13 ≤ 1,600 m³/h |
Prefilter |
G4 Z-line (EN 779:2002) |
High-temperature particulate air filter |
TROTEC HEPA H14, EN 1822 (standard minipleat) Each filter is tested and certified individually. |
Filter change interval |
Max. 1 to 2 years |
Filter change indication |
– |
FlowMatic control |
– |
Safety and filter hygiene: Thermal decontamination and filter regeneration at approx. 100 °C. 15 min. heating-up phase / 15 min. decon phase (altogether 30 min.) |
No thermal decontamination and reconditioning of the filter |
Mains connection (connector plug) |
220–240 V 50 / 60 Hz (CEE 7/7, H07RN-F) |
ø power consumption |
0.15 kW* |
Exemplary total energy consumption (with 900 m³/h air volume) |
approx. 1.2 kWh per day / approx. 24 kWh per month* |
Control panel |
Manual control panel (6-step switch) |
Dimensions L x W x H (mobile housing) |
– |
Dimensions L x W x H (stationary housing) |
506 x 523 x 1,100 mm to 2,100 mm ** Width with optional sound protection caps: 770 mm |
Weight (mobile housing) |
– |
Weight (stationary housing) |
73 kg (incl. filter) |
* for a 5-day week with 8 h operating time per day and 900 m³ air volume ** depending on the FlowExtender Silence+ attachment |
TAC XT |
Available colour versions |
Yellow |
Also available as stainless steel version |
✓ |
TAC V+ |
Available colour versions |
Yellow, basalt grey, white, bronze |
Also available as stainless steel version |
✓ |
TAC M |
Available colour versions |
Yellow, basalt grey, white, bronze |
Also available as stainless steel version |
– |
TAC ECO |
Available colour versions |
Basalt grey |
Also available as stainless steel version |
– |
TAC BASIC |
Available colour versions |
Basalt grey |
Also available as stainless steel version |
– |
Stainless steel version for hygiene-sensitive areas
The high-performance air purifier TAC V+ as well as the multi air handler TAC XT are optionally also available in stainless steel design, which is ideally suited for the use in areas with specific hygiene requirements or especially reactive atmospheres.
The stainless steel housing is easy to clean and manufactured of the material 1.4301, which features a very high corrosion resistance and which is particularly resistant to various chemical solutions.
TAC V+ Dual for virus filtration in large halls
For virus-free air purification of even very large hall areas we recommend using the TAC V+ Dual. This special model that blows out clean air on both sides offers you all advantages of the TAC V+ basic model, including the unique thermal filter decontamination and regeneration function.
With its high-pressure fan and the special filter equipment, the effectiveness of which has been proven, the Dual design, which draws in air at the floor side and blows it out on two sides, makes it possible to extensively flush even spacious hall areas with virus-free, filtered clean air.
C profiles integrated on both sides allow you to flexibly mount the TAC V+ Dual on the ceiling or wall, in the process of which you can also remove the control panel of the TAC V+ from the unit and attach it near the floor by cable, for example on mounting columns or the hall wall, also making it possible to easily control the high-performance air purifier from a distance even if the TAC V+ Dual has been mounted at a great height.
With the stainless steel version you can even use the TAC V+ Dual, which is available with a variety of clean air capacities on request, in hygiene-sensitive areas without any restrictions. Just contact our experts, we would be happy to advise you personally.
Learn more about the technical possibilities of virus air filtration
You want to know which technical aids offer effective protection against viruses in the room air? Do you have any questions with regard to the different cleaning methods offered on the market, their functional principle and their suitability for virus filtration? Visit our air cleaner-FAQ for virus filtration – Here you'll find answers to all of your questions with regard to air purification, virus filtration, standards as well as filter classes and of course the high-performance air purifier TAC V+ ...
High-performance air purifiers “made in Germany” for effective health protection
Trotec offers you the perfect air purification solution for every requirement:
Not only mobile, but also stationary: high-performance air purifiers of the TAC series for highly frequented medium-sized and larger rooms
All TAC high-performance air purifiers, such as the TAC V+, are guarantors for clean, filtered and pure air and our best recommendation for effective health protection in larger rooms where many people are staying, working, playing, learning or shopping.
Different model variants ensure that the optimum TAC high-performance air purifier is available for every need. In addition to the mobile version for easy changes of location, all models are also available as a stationary version – providing a clean design solution for clean air on the spot!
Continue to the model and design variants of the TAC high-performance air purifiers ...
In good shape for good air: comfort high-performance air purifier AirgoClean® One for smaller shops, offices, practices, law firms or exclusive private rooms
Being one size smaller in terms of dimensions, our comfort high-performance air purifier AirgoClean® One at the same time impresses with remarkable performance data in this device class.
Performance, comfort and design combined in perfect harmony is what makes the AirgoClean® One the first choice for all users who want to ensure a healthy feel-good climate with clean, good air in their rooms and who do not want to do without convenient functions and a first-class design.
Continue to the high-performance air purifier AirgoClean® One ...
Buy
Techn. data TAC V+
Mobile version
Technical data | ||
---|---|---|
General information | ||
Article number | 1.580.001.152 | |
Dust class | ||
as per DIN EN 60335-2-69 | H | |
as per DIN EN 1822 (ISO 45H filter ISO 29463) | H14 | |
as per DIN EN 779:2002 | F7 | |
Air flow rate | ||
Max. air volume flow [m³/h] | 2,100 | |
Suitable for rooms sized up to [m²/m³] with H14 filter class | 80 m² /200 m³ | |
Recommended amount of air for HighFlow filter with filter class H14 ≤ [m³/h] | 1,200 | |
Recommended amount of air for HighFlow filter with filter class H13 ≤ [m³/h]] | 2,100 | |
Electrical values | ||
Mains connection | 220 - 240 V, 50/60 Hz | |
Power consumption without thermal decontamination at 900 m³ / h air volume [kW] | 0.16 | |
Power consumption with thermal decontamination (60 min) [kW] | 1.25 | |
Nominal current consumption [A] | 5.5 | |
Recommended fusing [A] | 10 | |
Electric connection | ||
Connection plug | CEE 7/7, H07RN-F | |
Cable length [m] | 4 | |
Sound values | ||
Depending on the configuration (sound protection caps, FlowExtender) | 29 - 50 dB(A) | |
Fan | ||
Radial | ||
axial | ||
stages | 7 | |
Safety feature | ||
Protection class | IP20 | |
Dimensions | ||
Length (packaging excluded) [mm] | 690 | |
Width (packaging excluded) [mm] | 610 | |
Height (packaging excluded) [mm] | 1,300 | |
Weight | ||
(packaging excluded) [kg] | 89 |
Equipment, features and functions | ||
---|---|---|
Equipment | ||
Thermal filter decontamination | ||
Thermal filter regeneration | ||
Touchscreen | ||
Usage-related, sensor-controlled filter change indication of the F7 prefilter | ||
Usage-related, sensor-controlled filter change indication of the H14 main filter | ||
FlowMatic control | ||
Timer switch for the device is flexibly adjustable | ||
Timer switch for thermal decontamination is flexibly adjustable | ||
Operating hours counter | ||
Update of the control software via USB flash drive | ||
Language setting | ||
Key lock | ||
Silence mode | ||
Filter change indication | ||
Pre-filter | ||
Main filter | ||
Filter | ||
combination Hygienic areas (≥ 15 ACH) | F7 + H14 | |
Suitable for rooms sized up to Hygienic areas (≥ 15 ACH) [m³] | 107 | |
Mobility | ||
Carry/transport handle(s) | ||
Trestle rollers/ fixed castors | ||
Non-marking rubber wheels/rollers | ||
Foot | ||
Protective bar at the control panel | ||
Full-rubber guide wheels | ||
Guiding wheels pneumatic tyres | ||
Stacking frame | ||
Forklift pockets | ||
Shock protection frame |
standard equipment
optionally available
not available
Tower version
Technical data | ||
---|---|---|
General information | ||
Article number | 1.580.010.152 | |
Dust class | ||
as per DIN EN 60335-2-69 | H | |
as per DIN EN 1822 (ISO 45H filter ISO 29463) | H14 | |
as per DIN EN 779:2002 | F7 | |
Air flow rate | ||
Max. air volume flow [m³/h] | 2,100 | |
Suitable for rooms sized up to [m²/m³] with H14 filter class | 80 m² /200 m³ | |
Recommended amount of air for HighFlow filter with filter class H14 ≤ [m³/h] | 1,200 | |
Recommended amount of air for HighFlow filter with filter class H13 ≤ [m³/h] | 1,800 | |
Electrical values | ||
Mains connection | 220 - 240 V, 50/60 Hz | |
Power consumption without thermal decontamination at 900 m³ / h air volume [kW] | 0.16 | |
Power consumption with thermal decontamination (60 min) [kW] | 1.25 | |
Nominal current consumption [A] | 5.5 | |
Recommended fusing [A] | 10 | |
Electric connection | ||
Connection plug | CEE 7/7, H07RN-F | |
Cable length [m] | 4 | |
Sound values | ||
Depending on the configuration (sound protection caps, FlowExtender) | 29 - 50 dB(A) | |
Fan | ||
Radial | ||
axial | ||
stages | 7 | |
Safety feature | ||
Protection class | IP20 | |
Dimensions | ||
Length (packaging excluded) [mm] | 506 | |
Width (packaging excluded) [mm] | 523 | |
Height (packaging excluded) [mm] | 1,270 | |
Weight | ||
(packaging excluded) [kg] | 89 |
Equipment, features and functions | ||
---|---|---|
Equipment | ||
Thermal filter decontamination | ||
Thermal filter regeneration | ||
Touchscreen | ||
Usage-related, sensor-controlled filter change indication of the F7 prefilter | ||
Usage-related, sensor-controlled filter change indication of the H14 main filter | ||
FlowMatic control | ||
Timer switch for the device is flexibly adjustable | ||
Timer switch for thermal decontamination is flexibly adjustable | ||
Operating hours counter | ||
Update of the control software via USB flash drive | ||
Language setting | ||
Key lock | ||
Silence mode | ||
Filter change indication | ||
Pre-filter | ||
Main filter | ||
Filter | ||
combination Hygienic areas (≥ 15 ACH) | F7 + H14 | |
Suitable for rooms sized up to Hygienic areas (≥ 15 ACH) [m³] | 107 | |
Mobility | ||
Carry/transport handle(s) | ||
Trestle rollers/ fixed castors | ||
Non-marking rubber wheels/rollers | ||
Foot | ||
Protective bar at the control panel | ||
Full-rubber guide wheels | ||
Guiding wheels pneumatic tyres | ||
Stacking frame | ||
Forklift pockets | ||
Shock protection frame |
standard equipment
optionally available
not available
Techn. data TAC M
Mobile version
Technical data | ||
---|---|---|
General information | ||
Article number | 1.580.001.145 | |
Dust class | ||
as per DIN EN 1822 (ISO 45H filter ISO 29463) | H14 | |
as per DIN EN 779:2002 | F7 | |
Air flow rate | ||
Max. air volume flow [m³/h] | 2,100 | |
Suitable for rooms sized up to [m²/m³] with H14 filter class | 80 m² /200 m³ | |
Recommended amount of air for HighFlow filter with filter class H14 ≤ [m³/h] | 1,200 | |
Recommended amount of air for HighFlow filter with filter class H13 ≤ [m³/h]] | 2,100 | |
Electrical values | ||
Mains connection | 220 - 240 V, 50/60 Hz | |
Power consumption without thermal decontamination at 900 m³ / h air volume [kW] | 0.16 | |
Nominal current consumption [A] | 3.5 | |
Recommended fusing [A] | 6 | |
Electric connection | ||
Connection plug | CEE 7/7, H07RN-F | |
Cable length [m] | 4 | |
Sound values | ||
Depending on the configuration (sound protection caps, FlowExtender) | 29 - 50 dB(A) | |
Fan | ||
Radial | ||
axial | ||
stages | 7 | |
Safety feature | ||
IP23 | ||
Dimensions | ||
Length (packaging excluded) [mm] | 690 | |
Width (packaging excluded) [mm] | 610 | |
Height (packaging excluded) [mm] | 1,300 | |
Weight | ||
(packaging excluded) [kg] | 84 |
Equipment, features and functions | ||
---|---|---|
Equipment | ||
Touchscreen | ||
Usage-related, sensor-controlled filter change indication of the F7 prefilter | ||
Usage-related, sensor-controlled filter change indication of the H14 main filter | ||
FlowMatic control | ||
Timer switch for the device is flexibly adjustable | ||
Key lock | ||
Update of the control software via USB flash drive | ||
Operating hours counter | ||
Language setting | ||
Silence mode | ||
Filter change indication | ||
Pre-filter | ||
Main filter | ||
Filter | ||
combination Hygienic areas (≥ 15 ACH) | F7 + H14 | |
Suitable for rooms sized up to Hygienic areas (≥ 15 ACH) [m³] | 107 | |
Mobility | ||
Carry/transport handle(s) | ||
Trestle rollers/ fixed castors | ||
Non-marking rubber wheels/rollers | ||
Foot | ||
Protective bar at the control panel | ||
Full-rubber guide wheels | ||
Guiding wheels pneumatic tyres | ||
Stacking frame | ||
Forklift pockets | ||
Shock protection frame |
standard equipment
optionally available
not available
Tower version
Technical data | ||
---|---|---|
General information | ||
Article number | 1.580.010.145 | |
Dust class | ||
as per DIN EN 1822 (ISO 45H filter ISO 29463) | H14 | |
as per DIN EN 779:2002 | F7 | |
Air flow rate | ||
Max. air volume flow [m³/h] | 2,100 | |
Suitable for rooms sized up to [m²/m³] with H14 filter class | 80 m² /200 m³ | |
Recommended amount of air for HighFlow filter with filter class H14 ≤ [m³/h] | 1,200 | |
Recommended amount of air for HighFlow filter with filter class H13 ≤ [m³/h]] | 1,800 | |
Electrical values | ||
Mains connection | 220 - 240 V, 50/60 Hz | |
Power consumption without thermal decontamination at 900 m³ / h air volume [kW] | 0.16 | |
Nominal current consumption [A] | 3.5 | |
Recommended fusing [A] | 6 | |
Electric connection | ||
Connection plug | CEE 7/7, H07RN-F | |
Cable length [m] | 4 | |
Sound values | ||
Depending on the configuration (sound protection caps, FlowExtender) | 29 - 50 dB(A) | |
Fan | ||
Radial | ||
axial | ||
stages | 7 | |
Safety feature | ||
Protection class | IP20 | |
Dimensions | ||
Length (packaging excluded) [mm] | 506 | |
Width (packaging excluded) [mm] | 523 | |
Height (packaging excluded) [mm] | 1,100 | |
Weight | ||
(packaging excluded) [kg] | 84 |
Equipment, features and functions | ||
---|---|---|
Equipment | ||
Touchscreen | ||
Usage-related, sensor-controlled filter change indication of the F7 prefilter | ||
Usage-related, sensor-controlled filter change indication of the H14 main filter | ||
FlowMatic control | ||
Timer switch for the device is flexibly adjustable | ||
Key lock | ||
Update of the control software via USB flash drive | ||
Operating hours counter | ||
Language setting | ||
Silence mode | ||
sound protection hood | ||
Flowstop shutters | ||
Hose adapter | ||
Manipulation protection | ||
Filter change indication | ||
Pre-filter | ||
Main filter | ||
Filter | ||
combination Hygienic areas (≥ 15 ACH) | F7 + H14 | |
Suitable for rooms sized up to Hygienic areas (≥ 15 ACH) [m³] | 107 | |
Mobility | ||
Carry/transport handle(s) | ||
Trestle rollers/ fixed castors | ||
Non-marking rubber wheels/rollers | ||
Foot | ||
Protective bar at the control panel | ||
Full-rubber guide wheels | ||
Guiding wheels pneumatic tyres | ||
Stacking frame | ||
Forklift pockets | ||
Shock protection frame |
standard equipment
optionally available
not available
Techn. data TAC ECO
Mobile version
Technical data | ||
---|---|---|
General information | ||
Article number | 1.580.001.140 | |
Dust class | ||
as per DIN EN 1822 (ISO 45H filter ISO 29463) | H14 | |
as per DIN EN 779:2002 | G4 Z-line | |
Air flow rate | ||
Suitable for rooms sized up to [m²/m³] | 80 m² /200 m³ | |
Max. air volume flow [m³/h] | 1,600 | |
Recommended amount of air for standard filter with filter class H14 ≤ [m³/h] | 1,000 | |
Recommended amount of air for standard filter with filter class H13 ≤ [m³/h] | 1,600 | |
Electrical values | ||
Mains connection | 220 - 240 V, 50/60 Hz | |
Power consumption without thermal decontamination at 900 m³ / h air volume [kW] | 0.16 | |
Nominal current consumption [A] | 3.5 | |
Recommended fusing [A] | 6 | |
Electric connection | ||
Connection plug | CEE 7/7, H07RN-F | |
Cable length [m] | 4 | |
Sound values | ||
Depending on the configuration (sound protection caps, FlowExtender) | 29 - 50 dB(A) | |
Fan | ||
Radial | ||
axial | ||
stages | 6 | |
Safety feature | ||
Protection class | IP20 | |
Dimensions | ||
Length (packaging excluded) [mm] | 690 | |
Width (packaging excluded) [mm] | 610 | |
Height (packaging excluded) [mm] | 1,130 | |
Weight | ||
(packaging excluded) [kg] | 84 |
Equipment, features and functions | ||
---|---|---|
Equipment | ||
Manual control panel | ||
Usage-related, sensor-controlled filter change indication of the G4 prefilter | ||
Usage-related, sensor-controlled filter change indication of the H14 main filter | ||
Silence mode | ||
Filter change indication | ||
Pre-filter | ||
Main filter | ||
Filter | ||
combination Hygienic areas (≥ 15 ACH) | G4 + H14 | |
Suitable for rooms sized up to Hygienic areas (≥ 15 ACH) [m³] | 107 | |
Mobility | ||
Carry/transport handle(s) | ||
Trestle rollers/ fixed castors | ||
Non-marking rubber wheels/rollers | ||
Foot | ||
Full-rubber guide wheels | ||
Guiding wheels pneumatic tyres | ||
Stacking frame | ||
Forklift pockets | ||
Shock protection frame |
standard equipment
optionally available
not available
Tower version
Technical data | ||
---|---|---|
General information | ||
Article number | 1.580.010.140 | |
Dust class | ||
as per DIN EN 1822 (ISO 45H filter ISO 29463) | H14 | |
as per DIN EN 779:2002 | G4 Z-line | |
Air flow rate | ||
Suitable for rooms sized up to [m²/m³] | 80 m² /200 m³ | |
Max. air volume flow [m³/h] | 1,600 | |
Recommended amount of air for standard filter with filter class H14 ≤ [m³/h] | 1,000 | |
Recommended amount of air for standard filter with filter class H13 ≤ [m³/h] | 1,600 | |
Electrical values | ||
Mains connection | 220 - 240 V, 50/60 Hz | |
Power consumption without thermal decontamination at 900 m³ / h air volume [kW] | 0.16 | |
Nominal current consumption [A] | 3.5 | |
Recommended fusing [A] | 6 | |
Electric connection | ||
Connection plug | CEE 7/7, H07RN-F | |
Cable length [m] | 4 | |
Sound values | ||
Depending on the configuration (sound protection caps, FlowExtender) | 29 - 50 dB(A) | |
Fan | ||
Radial | ||
axial | ||
stages | 6 | |
Safety feature | ||
Protection class | IP20 | |
Dimensions | ||
Length (packaging excluded) [mm] | 506 | |
Width (packaging excluded) [mm] | 523 | |
Height (packaging excluded) [mm] | 1,100 | |
Weight | ||
(packaging excluded) [kg] | 84 |
Equipment, features and functions | ||
---|---|---|
Equipment | ||
Manual control panel | ||
Usage-related, sensor-controlled filter change indication of the G4 prefilter | ||
Usage-related, sensor-controlled filter change indication of the H14 main filter | ||
Silence mode | ||
Filter change indication | ||
Pre-filter | ||
Main filter | ||
Filter | ||
combination Hygienic areas (≥ 15 ACH) | G4 + H14 | |
Suitable for rooms sized up to Hygienic areas (≥ 15 ACH) [m³] | 107 | |
Mobility | ||
Carry/transport handle(s) | ||
Trestle rollers/ fixed castors | ||
Non-marking rubber wheels/rollers | ||
Foot | ||
Full-rubber guide wheels | ||
Guiding wheels pneumatic tyres | ||
Stacking frame | ||
Forklift pockets | ||
Shock protection frame |
standard equipment
optionally available
not available
Techn. data TAC BASIC
Technical data | ||
---|---|---|
General information | ||
Article number | 1.580.001.139 | |
Dust class | ||
as per DIN EN 1822 (ISO 45H filter ISO 29463) | H14 | |
as per DIN EN 779:2002 | G4 Z-line | |
Air flow rate | ||
Suitable for rooms sized up to [m²/m³] | 80 m² /200 m³ | |
Max. air volume flow [m³/h] | 1,600 | |
Recommended amount of air for standard filter with filter class H14 ≤ [m³/h] | 1,000 | |
Recommended amount of air for standard filter with filter class H13 ≤ [m³/h] | 1,600 | |
Electrical values | ||
Mains connection | 220 - 240 V, 50/60 Hz | |
Power input [kW] | 0.75 | |
Power consumption without thermal decontamination at 900 m³ / h air volume [kW] | 0.16 | |
Recommended fusing [A] | 6 | |
Electric connection | ||
Connection plug | CEE 7/7, H07RN-F | |
Cable length [m] | 4 | |
Sound values | ||
Depending on the configuration (sound protection caps, FlowExtender) | 31 - 50 db(A) | |
Fan | ||
Radial | ||
axial | ||
stages | 6 | |
Safety feature | ||
Protection class | IP20 | |
Dimensions | ||
Length (packaging excluded) [mm] | 506 | |
Width (packaging excluded) [mm] | 523 | |
Height (packaging excluded) [mm] | 1,100 | |
Weight | ||
(packaging excluded) [kg] | 85 |
Equipment, features and functions | ||
---|---|---|
Equipment | ||
Manual control panel | ||
Silence mode | ||
Filter | ||
combination Hygienic areas (≥ 15 ACH) | G4 + H14 | |
Suitable for rooms sized up to Hygienic areas (≥ 15 ACH) [m³] | 107 | |
Mobility | ||
Swivel casters with parking brakes | ||
Feet |
standard equipment
optionally available
not available