TKL service for you:
Capacity Calculation
direct to calculation »
Unique in Europe!!
TKL for sublessors
Let us inform you about the multifaceted benefits of cooperation.
Condenser dryer TTK 3000 BYF (Stainless steel version)
Article number: 1120001120
Daily rent
Contact us by telephone: +49 2452 962 160 Contact us by telephone: +49 2452 962 160
Show net price (VAT not included)
Contact us by telephone: +49 2452 962 160 Contact us by telephone: +49 2452 962 160
Show net price (VAT not included)
Details
Technical data | ||
---|---|---|
General information | ||
Article number | 1.120.001.120 | |
Dehumidification performance | ||
At 20 °C / 60 % RH [l/24h] | 220 | |
At 30 °C / 80 % RH [l/24h] | 520 | |
Air flow rate | ||
Level Max. [m³/h] | 5,000 | |
Operating range | ||
Min. temperature [°C] | -15 | |
Max. temperature [°C] | 40 | |
Min. humidity [% RH] | 30 | |
Max. humidity [% RH] | 90 | |
Electrical values | ||
Mains connection | 400 V, 50 Hz | |
Nominal current consumption [A] | 16 | |
Power input [kW] | 7.3 | |
Required current starting phase [A] | 66 | |
Recommended fusing [A] | 25 | |
Electric connection | ||
Connection plug | CEE 32 A red | |
Heat emission | ||
kW | 14.7 | |
Coefficient of performance (COP) | 3.1 | |
Compressor | ||
refrigerant | R-407C | |
Amount of refrigerant [g] | 10,000 | |
GWP factor | 1,774 | |
CO2 equivalent [t] | 17.74 | |
Pressure suction side [MPa] | 0.7 | |
Pressure outlet side [MPa] | 2.7 | |
Sound values | ||
Distance 3 m [dB(A)] | 66 | |
Dimensions | ||
Length (packaging excluded) [mm] | 720 | |
Width (packaging excluded) [mm] | 980 | |
Height (packaging excluded) [mm] | 1,435 | |
Weight | ||
(packaging excluded) [kg] | 220 |
standard equipment
optionally available
not available
Combination products
Loading...
Accessories