Technical data |
Article number |
3.510.205.042
|
3.510.205.043
|
3.510.206.042
|
3.510.206.043
|
3.510.004.005
|
3.510.004.007
|
Min. measuring range | Air flow rate [m/s] |
1.1
|
1
|
0.6
|
0
|
0.1
|
1
|
Max. measuring range | Air flow rate [m/s] |
30
|
30
|
30
|
30
|
25
|
80
|
Accuracy | Air flow rate [%] |
3
|
3
|
3.5
|
|
5
|
2.5
|
Accuracy ± | Air flow rate [m/s] |
0.3
|
0.2
|
0.2
|
|
1
|
|
Resolution | Air flow rate [m/s] |
0.01
|
0.01
|
0.1
|
0.01
|
0.01
|
0.01
|
Measuring principle | Air flow rate |
Vane
|
Vane
|
Vane
|
|
Hot-wire
|
Dynamic pressure probe (Pitot)
|
Min. measuring range | Air flow rate [mph] |
2.46
|
2.2
|
1.3
|
0
|
0.2
|
2.24
|
Max. measuring range | Air flow rate [mph] |
67
|
67
|
67
|
67
|
55.8
|
178.66
|
Accuracy | Air flow rate [%] |
3
|
3
|
3.5
|
|
5
|
|
Accuracy ± | Air flow rate [mph] |
0.4
|
0.4
|
0.4
|
|
1
|
|
Resolution | Air flow rate [mph] |
0.1
|
0.1
|
0.1
|
0.1
|
0.1
|
0.01
|
Min. measuring range | Air flow rate [km/h] |
3.96
|
3.6
|
2.2
|
0
|
0.3
|
3.6
|
Max. measuring range | Air flow rate [km/h] |
108
|
108
|
108
|
108
|
90
|
288
|
Accuracy | Air flow rate [%] |
3
|
3
|
3.5
|
|
5
|
|
Accuracy ± | Air flow rate [km/h] |
1
|
0.8
|
0.7
|
|
1
|
|
Resolution | Air flow rate [km/h] |
0.1
|
0.1
|
0.1
|
0.1
|
0.1
|
0.1
|
Min. measuring range | Air flow rate [kn] |
2.13
|
1.9
|
1.2
|
0
|
0.2
|
2
|
Max. measuring range | Air flow rate [kn] |
58
|
58
|
58
|
58
|
48.5
|
154.6
|
Accuracy | Air flow rate [%] |
3
|
3
|
3.5
|
|
5
|
|
Accuracy ± | Air flow rate [kn] |
0.4
|
0.4
|
0.4
|
|
1
|
|
Resolution | Air flow rate [kn] |
0.1
|
0.1
|
0.1
|
0.1
|
0.1
|
0.1
|
Min. measuring range | Air flow rate [ft/min] |
216
|
196
|
118
|
0
|
20
|
200
|
Max. measuring range | Air flow rate [ft/min] |
5,900
|
5,900
|
5,905
|
5,900
|
4,925
|
15,733
|
Accuracy | Air flow rate [%] |
3
|
3
|
3.5
|
|
5
|
|
Accuracy ± | Air flow rate [ft/min] |
40
|
40
|
39
|
|
1
|
|
Resolution | Air flow rate [ft/min] |
1
|
1
|
1
|
1
|
1
|
1
|
Min. measuring range | Air volume flow [m³/min] |
|
0
|
|
|
0.001
|
0
|
Max. measuring range | Air volume flow [m³/min] |
|
999.9
|
|
|
99,999
|
99,999
|
Resolution [m³/min] | Air volume flow |
|
|
|
|
0.001 – 100
|
0.001 – 100
|
Min. measuring range | Air volume flow [ft³/min] |
|
|
|
|
0.001
|
0
|
Max. measuring range | Air volume flow [ft³/min] |
|
|
|
|
99,999
|
99,999
|
Resolution [ft³/min] | Air volume flow |
|
|
|
|
0.001 – 100
|
0.0001 – 100
|
Min. measuring range | Air temperature [°C] |
|
-10
|
-20
|
-20
|
0
|
0
|
Max. measuring range | Air temperature [°C] |
|
60
|
60
|
60
|
50
|
50
|
Accuracy ± | Air temperature [°C] |
|
1.5
|
|
|
1
|
1
|
Accuracy – temperature |
|
±1.5 °C / ±3 °F
|
±0.8 °C (at <0 °C) ±0.5 °C (at ≥ 0 °C)
|
±0.8 °C (at -20 to 0 °C) ±0.5 °C (at 0 to 60°C)
|
|
|
Resolution [°C] |
|
0.1
|
0.1
|
0.1
|
0.1
|
0.1
|
Min. measuring range | Air temperature [°F] |
|
14
|
-4
|
-4
|
|
32
|
Max. measuring range | Air temperature [°F] |
|
140
|
140
|
140
|
|
122
|
Accuracy ± | Air temperature [°F] |
|
3
|
|
|
|
2
|
Resolution [°F] |
|
0.1
|
0.1
|
0.1
|
|
0
|
Measuring range |
|
|
|
|
|
0 bis 5,000 Pa
|
Resolution | Air pressure [PSI] |
|
|
|
|
|
0
|
Resolution | Air pressure [Pa] |
|
|
|
|
|
1
|
Max. measuring range | Air pressure [Pa] |
|
|
|
|
|
5,000
|
Min. measuring range | Air pressure [Pa] |
|
|
|
|
|
0
|
Resolution | Air pressure [inH2O] |
|
|
|
|
|
0.01
|
Max. measuring range | Air pressure [inH2O] |
|
|
|
|
|
20.07
|
Min. measuring range | Air pressure [inH2O] |
|
|
|
|
|
0
|
Max. measuring range | Air pressure [PSI] |
|
|
|
|
|
0.725
|
Min. measuring range | Air pressure [mbar] |
|
|
|
|
|
0
|
Min. measuring range | Air pressure [PSI] |
|
|
|
|
|
0
|
Resolution | Air pressure [mmH2O] |
|
|
|
|
|
0.1
|
Max. measuring range | Air pressure [mmH2O] |
|
|
|
|
|
509.8
|
Min. measuring range | Air pressure [mmH2O] |
|
|
|
|
|
0
|
Resolution | Air pressure [mbar] |
|
|
|
|
|
0.01
|
Max. measuring range | Air pressure [mbar] |
|
|
|
|
|
50
|
Accuracy |
|
|
|
|
|
±0,3% bei +25 °C
|
Accuracy – relative humidity |
|
|
± 3.5 % RH (with 20 to 80 % RH) ± 5 % RH (with 0 to 20 % RH and 80 to 100 % RH)
|
±3.5 % RH (with 20 to 80 % RH) ± 5 % RH (with 0 to 20 % RH and 80 to 100 % RH)
|
|
|
Resolution | Relative humidity [%RH] |
|
|
0.1
|
|
|
|
Resolution | Relative humidity [%] |
|
|
|
0.1
|
|
|
LCD |
|
|
|
|
|
|
Monochrome |
|
|
|
|
|
|
Touch |
|
|
|
|
|
|
USB |
|
|
|
|
|
|
Plastics |
|
|
|
|
|
|
Ø probe tip/base |
|
|
|
|
10 mm/ 12 mm
|
|
Metal |
|
|
|
|
|
|
4.0 (BLE) |
|
|
|
|
|
|
Max. transmission range |
|
|
10 m in open terrain
|
10 m in open terrain
|
|
|
Internal (battery) |
|
|
|
|
|
|
External (USB) |
|
|
|
|
|
|
Battery type |
1 x 9 V battery
|
1 x 9 V battery
|
3 x 1.5 V, AAA
|
|
1 x 9V battery
|
1 x 9V battery
|
3 x 1.5 V, AAA |
|
|
|
|
|
|
Operation - min. temperature [°C] |
0
|
0
|
-20
|
-20
|
0
|
0
|
Operation - max. temperature [°C] |
50
|
50
|
50
|
50
|
50
|
50
|
Operation – min. relative humidity [%r.F.] |
|
|
10
|
10
|
|
|
Operation - max. relative humidity [%r.F.] |
|
|
90
|
90
|
|
|
Relative humidity during storage [%] |
|
|
< 80% RH
|
< 80% RH
|
|
|
Length (packaging excluded) [mm] |
167
|
165
|
22
|
22
|
210
|
210
|
Length Telescopic probe [mm] |
|
|
|
22
|
|
|
Width (packaging excluded) [mm] |
34
|
32
|
43
|
36
|
75
|
75
|
Width Telescopic probe [mm] |
|
|
|
36
|
|
|
Height (packaging excluded) [mm] |
56
|
54
|
158
|
320
|
50
|
50
|
Height Telescopic probe [mm] |
|
|
|
555
|
|
|
Diameter Telescopic probe [mm] |
|
|
|
12
|
|
|
(packaging excluded) [kg] |
0.139
|
0.27
|
0.122
|
0.122
|
0.28
|
0.54
|
Standard scope of delivery |
Measuring device |
|
|
|
|
|
|
Bag/holster |
|
|
|
|
|
|
Operating manual |
|
|
|
|
|
|
Storage case |
|
|
|
|
|
|
Wrist strap |
|
|
|
|
|
|
Dynamic pressure probe (Pitot) |
|
|
|
|
|
|
Connection hoses |
|
|
|
|
|
|
USB connection cable |
|
|
|
|
|
|
Telescopic probe |
|
|
|
|
|
|
Hard-shell case |
|
|
|
|
|
|
Transport bag |
|
|
|
|
|
|
Ascertainable measured values and functions |
Air flow rate [m/s] |
|
|
|
|
|
|
Temperature [°F] |
|
|
|
|
|
|
Air pressure [inH2O] |
|
|
|
|
|
|
Air pressure [PSI] |
|
|
|
|
|
|
Air pressure [mmH2O)] |
|
|
|
|
|
|
Air pressure [mbar] |
|
|
|
|
|
|
Wind speed [m/s] |
|
|
|
|
|
|
Relative humidity [%] |
|
|
|
|
|
|
Temperature [°C] |
|
|
|
|
|
|
Air flow rate [km/h] |
|
|
|
|
|
|
Air temperature [°F] |
|
|
|
|
|
|
Air temperature [°C] |
|
|
|
|
|
|
Air volume flow [ft³/min] |
|
|
|
|
|
|
Air volume flow [m³/min] |
|
|
|
|
|
|
Air flow rate [knots] |
|
|
|
|
|
|
Air flow rate [mph] |
|
|
|
|
|
|
Air flow rate [ft/min] |
|
|
|
|
|
|
Air pressure [Pa] |
|
|
|
|
|
|
Maximum value display |
|
|
|
|
|
|
Switching function °C/°F |
|
|
|
|
|
|
Display illumination |
|
|
|
|
|
|
Long-term measurement function |
|
|
|
|
|
|
Extendable telescopic probe |
|
|
|
|
|
|
Report generation function |
|
|
|
|
|
|
Data export |
|
|
|
|
|
|
Representation of measurement data as chart or table |
|
|
|
|
|
|
Alarm function |
|
|
|
|
|
|
Indication in m/s, km/h, m³/min, ft/min, mph, kn |
|
|
|
|
|
|
Battery status indication |
|
|
|
|
|
|
Backlit display |
|
|
|
|
|
|
m³/min (CMM) |
|
|
|
|
|
|
m/s, km/h, ft/min, mph, kn |
|
|
|
|
|
|
Temporal averaging calculation |
|
|
|
|
|
|
Multi-point averaging calculation |
|
|
|
|
|
|
Telescopic probe (1 m) |
|
|
|
|
|
|
Gooseneck probe (40 cm) |
|
|
|
|
|
|
Measured value hold function |
|
|
|
|
|
|
Minimum value display |
|
|
|
|
|
|
¼ inch tripod thread |
|
|
|
|
|
|
Sensor-controlled display illumination |
|
|
|
|
|
|
Automatic switch-off |
|
|
|
|
|
|
Average value display |
|
|
|
|
|
|
Dynamic pressure probe (Pitot) |
|
|
|
|
|
|