Multiple socket outlet PV4-MID+ from Trotec

Any questions?

We are happy to provide further information available.

Business: +49 2452 962 400
Industry: +49 2452 962 777
End-consumers: +49 2452 962 450

Lockable multiple socket outlet PV4-MID+

Handling the building site power supply in line with the regulations – easily done with the PV4-MID+

The PV4-MID+ is a smart composition of robust, lockable protective construction with built-in Trotec multiple socket outlet PV4-MID – all in one device and "made in Germany". As such the PV4-MID+ can easily warrant safe usage in accordance with DGUV, MID, MessEG and MessEV.

It's the inner values that matter – MID-compliant

Integrated within the protective construction you will find our solid multiple socket outlet PV4-MID with a hardwearing, solid rubber industrial housing. Underneath a lockable sealing cap this multiple socket outlet not only houses an energy consumption meter with an initial factory calibration according to MID* enabling the commercial application for billing purposes, it also comes equipped with a residual current circuit breaker (RCCB) thus meeting the requirements stipulated by the German Employer's Liability Insurance Association for the current consumption using sockets on construction and installation sites. The extremely robust housing with integrated carrying handle accommodates four safety sockets with self-closing hinged covers.

Everything properly secured thanks to the lockable protective construction

Further applicable in Germany in addition to the requirements of the European Measuring Instruments Directive are certain consumer obligations – under the heading MessEG (German Measurement and Calibration Act). Using the lockable multiple socket outlet PV4-MID+ ensures you are always on the safe side, for its robust, powder-coated steel sheet construction with lock hole for a lock or seal prevents tampering with the power consumer during operation. Therefore, the entire construction is optimally suited for use in accordance with the German Measurement and Calibration Act (MessEG) as well as the German Measurement and Calibration Ordinance (MessEV).

A few practical benefits:

  • Robust construction made of powder-coated sheet steel with integrated multiple socket outlet PV4-MID
  • For an application in accordance with the German Measurement and Calibration Act (MessEG) as well as the German Measurement and Calibration Ordinance (MessEV)
  • Quality product "made in Germany"
  • Ideal for rough operating conditions on ever-changing construction sites
  • DGUV-compliant
  • Residual current device and energy consumption meter protected underneath lockable sealing cap
  • Four safety sockets with self-closing hinged covers
  • Multiple socket outlet with hardwearing, solid rubber industrial housing
  • IP54 type of protection for use in construction sites, in wet rooms or outdoors
  • Oil- and UV-resistant cable (H07RN-F)

The PV4-MID+ permits a building site power supply handling in line with the regulations – starting with the current consumption to consumption measurement for further calculations

The residual current circuit breaker (RCCB) and MID-compliant* energy consumption meter are integrated beneath a transparent sealing cap that can be locked by means of an optional U-lock.
Residual current device and MID-compliant energy consumption meter
The PV4-MID+ consists of multiple socket outlet PV4-MID incorporated in a robust, lockable and tamper-proof steel sheet construction.
PV4-MID+: PV4-MID plus lockable steel sheet construction
The interior height of the PV4-MID+ is geared to fit even extra-long plug types and offers slots for four devices.
Dimensioned for long plug types as well
You can prevent tampering during the application of the PV4-MID+ by affixing a seal or U-lock to the lock hole (U-lock not included in the scope of delivery).
Lock hole for U-lock or seal

Well informed by Trotec:

Legally required measurement and calibration obligations for water damage restoration and construction drying

In accordance with the current requirements of the German Measurement and Calibration Act (MessEG) and the appertaining German Measurement and Calibration Ordinance (MessEV) energy consumption meters used for billing purposes need to be calibrated or metrologically traceable to a corresponding device. MID*-compliant measuring devices meet these requirements.

Further applicable in Germany in addition to the requirements of the European Measuring Instruments Directive are certain consumer obligations, the violation of which is also a regulatory offence:

For instance, in case of integrated measuring devices display and inscriptions must be clearly visible and legible; if not properly labelled, a sign must be attached to the main unit as well. An appropriate documentation shall ensure the accountability of the determined measured values.

Further specifications have been defined by the authorities for external measuring devices such as multiple socket outlets with integrated MID meter: It must be ensured that no additional power consumers can be connected or the existing ones replaced by others whilst the device is in use.

Moreover, restoration companies are obliged to maintain a current meter list as well as to report all types of measuring devices intended for use – including built-in ones – to the responsible supervisory authority for calibration within six weeks after their initial operation. This notification as per §32 MessEG can be given online via eichamt.de.

The lockable multiple socket outlet PV4-MID+ offers you the extra bit of safety, for this smart protection device meets all calibration requirements of the MessEG.

Trotec promises investment security

Statutory requirements can change, but our quality pledge remains unaffected:

We at Trotec guarantee that our devices have not only been produced and equipped according to the currently applicable regulations and standards, but also in view of future requirements.

Insulation dryer, dehumidifier or multiple socket outlet: That way, even though you might still be unaware of a new regulation, you can be sure of purchasing a Trotec product compliant with all the relevant regulations.

Lockable multiple socket outlet PV4-MID+

* What does MID-compliant mean?

MID-compliant counters correspond to the European Measuring Instruments Directive (MID) 2004/22/EC that defines inter alia the requirements for active power meters used for billing purposes. This also applies to, say, the energy consumption measuring for recharging to insurance companies or customers. Such devices are supplied with the initial factory calibration valid for 16 years in case of electromechanical counters and 8 years in case of electronic counters. After this time they have to be recalibrated.

Buy

Details

Technical data
General information
  Article number 6.100.002.037
Electric connection
  Input voltage [V/Hz] 230 V AC, 50 Hz
  Connection power [kVA] 3.6
  Backup fuse max. [A] 16
  CEE 7/3 (Schuko socket type F)
  Number of sockets 4
  Connection plug CEE 7/7 (plug type F + E)
  Connection cable 2 m, H07RN-F 3G2,5
Residual current circuit breaker (RCCB)
  Type (RCCB) Type A, pulse current sensitivity
  Rated current RCCB [A] 25
  Rated fault current [A] 0.03
  Rated voltage RCCB 230 V AC, 50 Hz
  Rated load factor (RDF) 0.25
Power Meter
  Type (MID) MID certified, non-resettable
  Display 6-digit LC display
  Rated current [A] (MID) 0.25 A Imin, 45 A Imax, 5 A Iref
  Rated voltage MID 230 V AC, 50 Hz
  Accuracy class A
Housing design
  Rubber
  Standards BGI 608, DIN 49440-2, EN 50470-1, EN 50470-3, EN 61008-1, EN 61439-3, EN 62,262
  IP54
  Impact strength IK10 (housing), IK8 (sockets)
Surrounding conditions
  Operation - min. temperature [°C] -20
  Operation - max. temperature [°C] 45
  Operation - max. relative humidity (non-condensing) [%] 95
Dimensions
  Length (packaging excluded) [mm] 450
  Width (packaging excluded) [mm] 205
  Height (packaging excluded) [mm] 155
Weight
  (packaging excluded) [kg] 4.65

 standard equipment

 optionally available

 not available

Downloads

Bedienungsanleitung Steckdosenleiste PV4-MID

Bedienungsanleitung Steckdosenleiste PV4-MID

TRT-BA-PV4-MID-PV4-MID_-HS-002-DE.pdf (505 KB)

Download